Log:
valutazioni - 4, GPA: 4.3 ( )

Istruzioni per l'uso Johnson Controls, Modello SA PD 180 THRU 240

Produttore : Johnson Controls
File Size : 2.06 mb
File Nome :
Lingua di insegnamento: en
Vai a scaricare



Facilità d'uso


An anti-short cycle delay (ASCD) is utilized to prevent operation of a compressor too soon after its previous run. The ASCD is initiated on unit start-up and on any compressor reset or lockout. The Simplicity™ control board monitors the following inputs for each cooling system: • A high-pressure switch is factory installed to protect against excessive discharge pressure due to a blocked condenser coil or a condenser fan motor failure. During cooling operation, if a high-pressure limit switch opens, the Simplicity™ control board will de-energize the associated compressors and initiate the 5-minute ASCD. If the call for cool is still present at the end of the ASCD, the control board will re-energize the halted compressor. If a high-pressure switch opens three times within two hours of operation, the Simplicity™ control board will lockout the associated system compressors and will flash an error code (see Table 11). • A low-pressure switch to protect the unit against excessively low suction pressure is standard on all condensing units. If the low-pressure switch opens during normal operation, the Simplicity™ control board will deenergize the compressor, initiate the ASCD, and shut down the condenser fans. On startup, if the low-pressure switch opens, the Simplicity™ control board will monitor the low-pressure switch to make sure it closes within one minute. If it fails to close, the unit will shut down the associated compressor and begin an ASCD. If the call for cool is still present at the end of the anti-short cycle time delay, the control board will re-energize the halted compressor. If a low-pressure switch opens three times within one hour of operation, the Simplicity™ control board will lock-out the associated compressor and flash an error code (see Table 11). • An ambient air switch will lock out mechanical cooling at 40°F. If the product was equipped from the factory with the low ambient option the unit will operate down to 0°F. If the unit was not ordered with the factory low ambient option a field installed low ambient kit is available. The refrigerant systems are independently monitored and controlled. On any fault, only the associated system will be affected by any safety/preventive action. The other refrigerant system will continue to operate unless it is affected by the fault as well. Compressor Protection In addition to the external pressure switches, the compressors also have inherent (internal) protection. If there is an abnormal temperature rise in a compressor, the protector will open to shut down the compressor. The UCB incorporates features to minimize compressor wear and damage. An Anti-Short Cycle Delay (ASCD) is utilized to prevent operation of a compressor too soon after its previous run. Additionally, a minimum run time is imposed any time a compressor is energized. The ASCD is initiated on unit start-up and on any compressor reset or lock-out. Flash Codes The UCB will initiate a flash code associated with errors within the system. Refer to UNIT CONTROL BOARD FLASH CODES Table 11. Reset Remove the call for cooling, by raising thermostat setting higher than the conditioned space temperature. This resets any pressure or freezestat flash codes. Simplicity™ only has minimum run time in cool. Heat pump mode shuts off immediately. Sequence of Operation Continuous Blower By setting the room thermostat to “ON,” the low voltage control circuit from the “R” to “G” is completed and the supply air blower will operate continuously. Intermittent Blower With the room thermostat fan switch set to “AUTO” and the system switch set to either the “AUTO” or “HEAT” settings, the blower is energized whenever a cooling or heating operation is requested. The blower is energized after any specified delay associated with the operation. When energized, the indoor blower has a minimum run time of 30 seconds. Additionally, the indoor blower has a delay of 10 seconds between operations. Cooling Sequence Of Operation Single-Stage Heat Pump (PC090) A single stage thermostat is required to operate the heat pump in cooling mode. The reversing valve is energized during cooling mode. A continuous 24V signal is passed through the normally closed contacts of relay RY2 to the "O" terminal of the Defrost Control Board (DC). The normally closed relay DR-2 within DC energizes the solenoid (SOL) of the reversing valve. When the thermostat calls for cooling (Y1), the Simplicity control board (UCB) closes the coils of relay RY1 and contactor 1S Johnson Controls Unitary Products 430645-YiM-D-0610 M1 while sending a signal to one of the "CFAN" terminals on DC. • Relay RY1 controls the crankcase heater (CCH1). The normally closed contacts allow CCH1 to operate during unit shutdown. • Contactor M1 controls compressor COMPR1. The output signal from the remaining "CFAN" terminal on DC closes the coil of contactor M3. • Contactor M3 controls outdoor fans ODFAN1 & 2. After completing the specified time for ...

Questo manuale è adatto anche per i modelli :
Condizionatori - SA PC090 THRU 240 (2.06 mb)

Scrivi la tua opinione del dispositivo



Il messaggio
Il tuo nome :
Inserire le due cifre :
capcha





categorie