Facilità d'uso
In addition, the 6500S can be remotely activated from the fire detection control panel, allowing easy function testing during maintenance. This test simulates light obscuration by means of a motor-driven test filter. An external power supply is needed for the test unit, which can not be powered by the loop. Building Safety. Building Security. © LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52114-0 • FAX. +43 1 52114-27 OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED 6500 DBL LST EN 0804.PDF • PAGE 1 Specifications Operating voltage Supply through loop voltage Current consumption from loop 2mA (quiescent), 8mA (active) Ambient temperature -30°C to +55°C Relative humidity max. 95% (no condensation) Dimensions W x H x D 190 x 254 x 84 (mm), Smoke Detector 6500 200 x 230 x 10 (mm), Reflector (5m to 70m) Protection class IP54 Colour cream Weight 1.8kg Approval VdS G205033 Beam Smoke Detector 6500 Order number 244020 Order name Beam Smoke Detector/Anal./SS 6500 Beam Smoke Detector 6500S with test activation Operating voltage test unit 15 -32VDC Current consumption test unit 500mA Order number 244021 Order name Beam Smoke Detector/Test/Anal./SS 6500S Building Safety. Building Security. © LABOR STRAUSS SICHERUNGSANLAGENBAU GMBH • A-1231 WIEN • WIEGELESTRASSE 36 • TEL +43 1 52H4-0 • FAX +43 1 52114-27 OFFICE@LST.AT • WWW.LST.AT • ALL RIGHTS RESERVED 6500 DBL LST EN 0804.PDF • PAGE 2...