|
Facilità d'uso
Red flashes indicate motion detection by infrared technology. The sensor continually analyzes the parameters of the motion detection signal and adjusts its internal operation to maximize detection of motion while minimizing the effects of noise (electrical noise, air currents, temperature changes, etc.). Operation When the lights turn on, the sensor initially begins the Walk-through mode. Once the room is occupied for longer than 2.5 minutes, the sensor ends the Walk-through mode and begins the Occupied mode. When the sensor is first installed, the delayed-off time for the Occupied mode is based on the time adjustment settings. While the sensor is in use, the delayed-off time will change, based on how the sensor adapts to the room conditions. Whenever the sensor subsequently turns on, the value of the delayed-off time will be the adapted value (refer to Occupancy Pattern Learning For Delayed Off Time). The adapted settings can be reset using the DIP switch. Occupancy Pattern Learning For Delayed Off Time The sensor will automatically change the delayed off time in response to the occupancy and environmental conditions of the space where it is installed. The sensor analyzes the motion signal properties and will minimize the delayed off time duration when there is frequent motion detection, and lengthen the delayed off time duration when there is weak and infrequent motion detection. In the case of a false-off condition (lights turn off when the room is occupied), the delayed off time duration will immediately be lengthened to prevent further false turn offs. Occupancy Pattern Learning for Ultrasonic Technology The sensor learns the occupancy patterns of a space during the course of a day, for a seven day period. At any given time, the sensor will look at the collected data and adjust its ultrasonic sensitivity. The sensor will adjust the sensitivity to make it less likely to turn on during a period of non-occupancy and more likely to turn on during a period of occupancy. This adapting feature is not applicable when the sensor is using PIR functions only. The two tables (below and in the next column) and the “Minimum and Default Settings” illustration define the settings of the adjustment knobs and the DIP switches. * This setting is only used if the Single Technology Option (Switch A1) is selected. SWITCH FUNCTIONS Bank A OFF ON Single/Dual-Tech Mode Dual-Tech Single Tech PIR/Ultrasonic Mode PIR Ultrasonic Manual Mode Auto Adapting Enabled Auto Adapting Disabled Walk-Through Disable Walk-Through Enabled Walk-Through Disabled Bank B Override to ON Auto Mode Lights Forced ON Override to OFF Auto Mode Lights Forced OFF Test Mode OFF ON OFF = Enter/Exit Test Mode LEDs Disable LEDs Enabled LEDs Disabled DIP Switch Settings SWITCH SWITCH SETTINGS A1 A2* A3 A4 B1 B2 B3 B4 Field-of-View Ranges - GLS-ODT-C-2000 Field-of-View Ranges - GLS-ODT-C-1000 To set the Photocell level (used with the gray wire connection): 1. Remove the cover from the sensor. 2. Make note of the position of the red and green knobs. Rotate the red and green knobs fully CCW and enter the sensor’s Test mode as described above. 3. Rotate the blue knob fully CCW. 4. Wait for the lights to turn OFF. 5. Rotate the red knob fully CW. 6. Slowly rotate the blue knob clockwise until the lights turn ON. This is the correct setting. 7. Return the red and green knobs to their original positions 8. Replace the cover. Photocell level setting is complete. NOTE: This setting must be performed when the natural light is low enough to require artificial light. 1. ENSURE POWER IS ON. 2. Remove front cover. 3. Locate Dip Switch 3 in Bank B (B3). B3 will be in the OFF position from the factory. 4. To start Test mode, move switch to ON and back to OFF. The Test mode has now been initiated with a six second time-out. (Refer to the DIP Switch Settings table.) NOTE: If B3 is already in the ON position, then Test mode can be entered by just moving it to the OFF position. NOTE: The timer will remain in the six second Test mode for 15 minutes, then automatically exit Test mode and reset to the delayed-off time setting as defined by the black timer knob. NOTE: To manually take the timer out of the six second Test mode, simply toggle the switch B3 from OFF to ON and back to OFF. Set the delayed-off time to six seconds for performing a walk test. While the sensor is in Test mode, the LEDs will flash amber once a second. In order to use the ambient light override functionality of the sensor, the sensor must be wired to the GLS-SIM (or other compatible interface) using the gray wire instead of the blue wire. This feature allows the user to conserve energy by keeping the controlled lights off when not necessary. The sensor does this by measuring the amount of ambient light in the installed area and keeping the controlled lights off if there is enough ambient light available. To use this feature, the photocell adjustment (blue) knob must be adjusted from the default position. Once ...
Questo manuale è adatto anche per i modelli :Altri strumenti - GLS-ODT-C-500. GLS-ODT-C-1000 (706.31 kb)