|
Facilità d'uso
The external cabinet shall incorporate a built-in draft hood and shall be of baked enamel steel construction. It shall be suitable for installation on combustible flooring. The burners shall be a stainless steel stamped design and shall be mounted in a removable drawer assembly.The burner controls shall be 24 VAC and shall include slow-opening main gas valve for soft ignition, redundant safety shutoff gas valve, main and pilot pressure regulators, recycling intermittent pilot system with one-second shutdown in the event of pilot flame failure, automatic recycling high limit, manual reset ECO limit, main and pilot manual cocks and manual firing valve, and an ASME-rated pressure relief valve. The boiler shall be approved by Factory Mutual (FM).The boiler shall comply with current edition ASHRAE/IESNA 90.1. Optional: Factory-installed, dial-type temperature and pressure gauges shall be mounted on the front of the cabinet. For Technical Information and Automated Fax Service, call 800-527-1953. A.O. Smith Corporation reserves the right to make product changes or improvements without prior notice. July 2011R Page 4 of 4 AOSDG25300 ...
Questo manuale è adatto anche per i modelli :scaldabagno - DW-1810 (439.08 kb)
scaldabagno - DW-1810 (439.08 kb)
scaldabagno - DW-1810 (439.08 kb)