Log:
valutazioni - 2, GPA: 4 ( )

Istruzioni per l'uso Lennox Hearth, Modello PMC-LCDC

Produttore : Lennox Hearth
File Size : 1.49 mb
File Nome :
Lingua di insegnamento: en
Vai a scaricare



Facilità d'uso


Ne la forcez pas. 4. Fermez la soupape d’arret de la canalisation principale. 5. Fermez la porte du compartiment de controle du bas. 1. Pour une fermeture complete, tournez l’interrupteur mural a la position d’arret “OFF”. 2. Ouvrez la porte du compartiment de controle du bas. Interrupteur ON/OFF OFFINPSI ONCONTROL IGNITER Vue de face AVERTISSEMENT: SI VOUS NE SUIVEZ PAS CES INSTRUCTIONS A LA LETTRE, IL POURRAIT S’EN SUIVRE UN INCENDIE OU UNE EXPLOSION CAUSANT DES DOMMAGES MATERIELS, DES BLESSURES CORPORELLES OU MEME DES PERTES DE VIE. TROUBLESHOOTING THE MILLIVOLT GAS CONTROL SYSTEM TROUBLESHOOTING THE MILLIVOLT GAS CONTROL SYSTEM Important: Valve system troubleshooting should only be accomplished by a qualified service technician. SYMPTOM POSSIBLE CAUSES CORRECTIVE ACTION 1. Spark ignitor will not light pilot after repeated triggering of ignitor button. A. Defective ignitor (no spark at electrode). Check for spark at electrode and pilot; if no spark and electrode wire is properly connected, replace ignitor. B. Defective or misaligned electrode at pilot (spark at electrode). Using a match, light pilot. If pilot lights, turn off pilot and trigger the ignitor button again. If pilot lights, an improper gas mixture caused the bad lighting and a longer purge period is recommended. If pilot will not light – check gap at electrode and pilot – should be ..." to have a strong spark. If gap measures ...", replace pilot (Figure 9 on page 7). C. Gas supply pressure errant. Check inlet gas pressure. It should be within the limits as marked on the rating plate. D. Pilot orifice plugged. Clean or replace pilot orifice. 2. Pilot will not stay lit after carefully following the lighting instructions. A. Defective pilot generator (thermocouple). Check pilot flame, it must impinge on thermocouple (Figure 9 on page 7) Clean and/or adjust pilot for maximum flame impingement on thermocouple. Ensure that the connection between the valve and thermocouple are tight and secure. 3. Pilot burning, no gas to burner, Valve knob “ON,” Wall Switch “ON.” A. Wall switch or wires defective. Check wall switch and wires for proper connections. Jumper wire across terminals at wall switch, if burner comes on, replace defective wall switch. If okay, jumper wires across wall switch wires at valve, if burner comes on, wires are faulty or connections are bad. B. Thermopile may not be generating sufficient millivoltage. Check thermopile with millivolt meter. Take reading at thermopile terminals of gas valve. Should read 325 millivolts minimum with optional wall switch “OFF.” Replace faulty thermopile if reading is below specified minimum. C. Plugged burner orifice. Check burner orifice for stoppage and remove. 4. Frequent pilot/burner outage problem. A. Pilot flame may be too low or blowing (high) causing the pilot/ valve safety to drop out. Clean and/or adjust pilot flame for maximum flame impingement on thermocouple (Figure 9 on page 7). TROUBLESHOOTING THE ELECTRONIC IGNITION SYSTEM Not...

Questo manuale è adatto anche per i modelli :
Camini - NEC-FPDC (1.49 mb)
Camini - NEC-FPDC (1.49 mb)
Camini - NEC-FPDC (1.49 mb)
Camini - NEC-LCDC (1.49 mb)

Scrivi la tua opinione del dispositivo



Il messaggio
Il tuo nome :
Inserire le due cifre :
capcha





categorie